IRC Stair & Guard Rules: Riser, Tread, Handrail, Guards

The IRC numbers for a residential stair — 7¾ in max riser, 10 in min tread, 36 in guards — and the one thing every US builder must check first: which edition your state and town adopted.

IRC 2021 Clause IRC R311.7 Clause R312

The requirement

Under the IRC, a riser can be at most 7¾ in (196 mm) tall. A tread must be at least 10 in (254 mm) deep. You need a handrail on any flight with 4 or more risers, set 34 to 38 in above the nosings. Guards must be at least 36 in high (R312). First check which edition your state and town adopted.

You can check all of these with a tape. The two numbers that shape every step are the riser and the tread (R311.7).

  • Riser: how tall each step is. The cap is 7¾ in (196 mm). Go taller and the step is too big to climb safely. So you add a step to bring each one down. Every riser in a flight must be near equal. They can vary no more than 3/8 in top to bottom (R311.7.5.1).
  • Tread depth (the going): how deep each step is. Measure it nosing to nosing, front edge to front edge. The minimum is 10 in (254 mm) (R311.7.5.2).

Three more numbers keep the stair safe to use:

DimensionIRC minimum
Riser heightmax 7¾ in (196 mm)
Tread depthmin 10 in (254 mm)
Headroommin 6 ft 8 in (2032 mm) (R311.7.2)
Clear widthmin 36 in (914 mm) (R311.7.1)
Handrail height34–38 in (864–965 mm) above the nosing line (R311.7.8)
≤ 7¾ in (196 mm)≥ 10 in (254 mm)
IRC 2021 · R311.7

Keep every step in a flight the same height and the same depth. The IRC only allows that tiny 3/8 in spread. One odd step is where people trip.

Guards & barriers

A guard is the barrier that stops a fall off an open edge. The IRC ties it to the height of the drop, not to the stair itself.

RuleIRC figure
Guard heightmin 36 in (914 mm) (R312.1)
Fall-height triggerrequired where a walking surface is more than 30 in (762 mm) above the floor or grade below, within 36 in horizontally
Open-side stair guardmay sit 34–38 in where it doubles as the handrail
Opening — generala 4 in (102 mm) sphere must not pass through (R312.1.3)
Opening — open side of a stairup to 4⅜ in
Opening — riser/tread/rail triangleup to 6 in

So if you can fall more than 30 in, you need a guard at least 36 in high. The gaps in it must be tight too. A 4 in sphere must not pass through any opening (R312.1.3). That keeps a small child’s head out. The open side of a stair gets a little more room, up to 4⅜ in. So does the triangle formed by the riser, tread and bottom rail, up to 6 in.

Work it out on site

Say your floor-to-floor height is 105 in. You want an even set of steps.

  1. Pick how many risers. 105 ÷ 7¾ (the tallest a riser can be) = 13.5. You can’t have half a step, so round up to 14 risers. 105 ÷ 14 = 7.5 in per riser. That sits under the 7¾ limit. Good.
  2. Set the tread. Use a 10 in tread or deeper, so it clears the minimum.
  3. Check headroom and width. You need 6 ft 8 in of clear height above the pitch. You also need 36 in of clear width.

If 105 ÷ your riser count lands over 7¾, add a riser and divide again. Keep every step equal. These are example numbers. Plug your real floor-to-floor height into the calculator.

Do it in 5 seconds

Sources

  • IRC 2021, Section R311.7 — Stairways (riser, tread, headroom, width, handrail) and Section R312 — Guards (guard height, fall trigger, openings). Read the code at codes.iccsafe.org.
  • Adoption & edition caveat — read this first. The IRC is a model code. It has no force until your state and/or town adopts it, almost always with local amendments. Editions in force are a patchwork — many places are still on IRC 2018 or 2015 — and California (CRC), Wisconsin, New York City and Chicago run their own codes. The figures above are the base IRC 2021 (stable across 2015–2024), but the enforceable number is the adopted-and-amended edition where you build. Confirm the edition and amendments with your local building department before you set out. Footing sizes (R403.1) are not listed here on purpose — they’re table-driven by your soil-bearing and loads, so read your soil/load table, don’t copy a number.

State variations

These states apply requirements that differ from the national provisions for this rule.

  • California Adopted R312

    Current code: California Residential Code (2025)

    California requires guards at least 42 in (1067 mm) high — taller than the IRC's 36 in. Stair geometry (riser, tread, headroom) otherwise matches the IRC.

Frequently asked questions

What is the maximum riser height for stairs in the US?
Under the IRC, a riser can be no taller than 7¾ in (196 mm). A riser is the up-and-down face of a step. Every riser in the same flight must be near equal, within 3/8 in top to bottom. Check which edition your state and town adopted, since that version rules your job.
What is the minimum tread depth?
The IRC minimum tread depth is 10 in (254 mm). The tread is the flat part your foot lands on. You measure it nosing to nosing. As always, confirm the edition your local building department enforces.
Do I need a handrail, and how high?
You need a handrail on any flight with 4 or more risers. It sits 34 to 38 in (864–965 mm) above the line drawn across the stair nosings. Check your adopted edition, since a local amendment can change this.
When is a guard required and how high?
A guard is the barrier that stops a fall off the open side. You need one where a walking surface is more than 30 in (762 mm) above the floor or ground below, within 36 in horizontally. Guards must be at least 36 in (914 mm) high. One that doubles as the handrail may sit 34 to 38 in.
Which code edition applies to my job?
The IRC is a model code. It has no force until your state or town adopts it, almost always with amendments. Many places still run IRC 2018 or 2015. California, Wisconsin, NYC and Chicago run their own codes. Confirm the adopted and amended edition with your local building department first.